power equipment.
Technical indicators
1. Accuracy: Cx: ±(reading×1%+1pF)
tgδ: ±(reading×1%+0.00040)
2.Anti-interference: Variable frequency anti-interference, the above accuracy can be
reached under 200% interference.
3.Capacitance range: Internal HV: 3pF~60000pF/10kV 60pF~1μF/0.5kV
External HV: 3pF~0.3μF/10kV 60pF~1μF/0.5kV
Resolution: Maximum 0.001pF, 4 valid figures.
4.tgδ range: unlimited, 0.001% resolution, automatic identification for capacitance,
inductance and resistance of three tested articles.
5.Test current range: 10μA~1A
6.Internal HV: Set voltage range: 0.5~10kV, Maximum output current: 200mA
Buck-bust method: continuous stepless regulation
Test frequency: 45、50、55、60、65Hz single frequency
45/55Hz、55/65Hz、47.5/52.5Hz automatic dual variable frequency
Frequency accuracy: ±0.01Hz
7.External HV: For UST, maximum test current is 5A, and power frequency
or variable frequency is 40-70Hz
For GST, maximum test current is 10kV/5A, and power frequency
or variable frequency is 40-70Hz
8.CVT self-exciting low voltage output: Output voltage 3~50V,
Output current 3~30A
9.Measuring duration: About 40s, depending on measuring method
10.Input power supply: 180V~270VAC, 50Hz/60Hz±1%,
supplied by alternating current or generator
11.Computer interface: Standard RS232 interface
12.Printer: mini-type thermal printer
13.Environment temperature: -10℃~50℃
14.Relative humidity: <90%
15.Dimensions:460×360×350mm
16.Weight:30kg